Seismic Qualification of 1000 MW Power Equipment
SMiRT-21, New-Delhi India, 6-11 November 2011, Paper-V612
- Авторы : Kaneva A. , G.I. Varbanov , Tz.B. Todorova , [Alexey M. Berkovskiy] Берковский А.М., [Viktor V. Kostarev] Костарев В.В.
- Язык: English
- Страницы: 8
- Библио-ссылка
- Библиотека: Conference Papers
- Год: 2011
- Файл: Full-length-paper-V612.pdf
Посещения: 1659
Обзор
Автор Administration
This paper clarifies the seismic adequacy of installed equipment and electrical cable raceways in operating WWER 1000 type NPP:
The qualification approach is a combination of numerical analyses and GIP methodology in consideration of some specific features of WWER equipment, taking into account the as-built conditions and plant specific floor response spectra.
As result of the study the selected equipment is divided into 2 groups – equipment and cable raceways that are seismically qualified for Review Level Earthquake, equipment and cable raceways which require seismic upgrading.