Seismic Qualification of 1000 MW Power Equipment
SMiRT-21, New-Delhi India, 6-11 November 2011, Paper-V612
- Autors: : Костарев В.В. [Viktor V. Kostarev], Берковский А.М. [Alexey M. Berkovskiy], Kaneva A., G.I. Varbanov, Tz.B. Todorova
- Publisher: English
- Pages: 8
- N°: 28
- Library: Conference Papers
- Year: 2011
- File: Full-length-paper-V612
Hits: 1127
Review
This paper clarifies the seismic adequacy of installed equipment and electrical cable raceways in operating WWER 1000 type NPP:
The qualification approach is a combination of numerical analyses and GIP methodology in consideration of some specific features of WWER equipment, taking into account the as-built conditions and plant specific floor response spectra.
As result of the study the selected equipment is divided into 2 groups – equipment and cable raceways that are seismically qualified for Review Level Earthquake, equipment and cable raceways which require seismic upgrading.